the aquaforce BOOSTER SET

The AquaForce is a comprehensive turnkey solution designed to effortlessly enhance water flow and pressure while minimizing downtime.

This system features a pre-plumbed booster set available in single, twin, or triple configurations, paired with a pre-insulated break tank as standard. Equipped with a fully variable inverter, it regulates pump speed to meet any demand, ensuring consistent, quiet, and efficient water pressure.

product applications

DOMESTIC

HOSPITALITY

COMMERCIAL

INDUSTRIAL

PICKUP

Product ready for collection within 3-5 days

Delivery

Product shipped nationwide in 3-5  days

Support

Product support available between 8:30am -5pm

  • Flow rates up to 900 l/m
  • Pressure to 7.0 bar
  • WRAS approved pump sets
  • Variable speed inverters

Booster Set product features

  • Choice of single, twin, or triple booster set configurations
  • Anti-vibration mounts to reduce noise
  • Error code display for fault diagnostics
  • High efficiency motors for long life and optimal operation
  • Huge choice of tanks to meet every need
  • WRAS approved pumps
  • Variable speed inverters
  • WRAS approved expansion vessel

Tank Features & Options

  • Choice of one piece or two piece tanks
  • 500L to 6000L capacity
  • Fully WRAS approved
  • Fully insulated
  • Available with inlet sizes of 15mm, 22mm, 28mm, 35mm, 42mm, and 50mm
  • System comes mounted on steel frame 
  • Available in AG or AB tank options.

product downloads

SINGLE VARI-RS BOOSTER SPECIFICATIONS

vari-rs single dimensions
Model RefMid curve FlowMid Curve PressureDN1DN2HH1H2LPower SupplykWHPFLC (amp)
1RS302/8DPT50 l/m1.5 bar1”1”700803103601x240v0.450.62.3
1RS305/8DPT50 l/m4.0 bar1”1”700803104081x240v0.751.03.0
1RS306/8DPT50 l/m4.5 bar1”1”700803104441x240v0.91.24.3
1RS307/8DPT50 l/m5.0 bar1”1”700803105181x240v1.31.85.6
1RS308/8DPT50 l/m5.25 bar1”1”700803105421x240v1.31.85.6
1RS502/8DPT75 l/m1.75 bar1¼”1”700803103601x240v0.450.62.3
1RS505/9DPT75 l/m4.5 bar1¼”1”700803104701x240v1.31.85.6
1RS506/8DPT75 l/m5.0 bar1¼”1”700803104981x240v1.31.85.6
1RS507/8DPT75 l/m6.5 bar1¼”1”700803105191x240v1.52.06.3
1RS508/8DPT75 l/m7.0 bar1¼”1”700803105431x240v2.23.08.2
1RS1002/8DPT160 l/m1.8 bar1½”1¼”700803103791x240v0.751.03.0
1RS1003/8DPT160 l/m2.5 bar1½”1¼”700803104411x240v1.31.85.6
1RS1004/8DPT160 l/m3.5 bar1½”1¼”700803104721x240v1.52.06.3
1RS1005/8DPT160 l/m4.0 bar1½”1¼”700803105021x240v2.23.08.2
1RS1006/8DPT160 l/m5.0 bar1½”1¼”700803105321X240V2.23.08.2

TWIN VARI-RS BOOSTER SPECIFICATIONS

Vari-RS Twin Dimensions
Model RefMid Curve FlowMid Curve PressureDN1DN2BHH1LMPower SupplykWHPFLC (amp)
2RS302/8DPT100 l/m1.5 bar2”1½”6409001356085401x240v2x0.452x0.62x2.3
2RS305/8DPT100 l/m4.0 bar2”1½”6409001356565401x240v2x0.752x1.02x3.0
2RS306/8DPT100 l/m4.5 bar2”1½”6409001356805401x240v2x0.92x1.22x4.3
2RS307/8DPT100 l/m5.0 bar2”1½”6409001357045401x240v2x1.32x1.82x5.6
2RS308/8DPT100 l/m5.25 bar2”1½”6409001357285401x240v2x1.32x1.82x5.6
2RS502/8DPT150 l /m1.75 bar2”1½”6409001356085401x240v2x0.452x0.62x2.3
2RS505/8DPT150 l /m4.5 bar2”1½”6409001356565401x240v2x1.32x1.82x5.6
2RS506/8DPT150 l /m5.0 bar2”1½”6409001356805401x240v2x1.32x1.82x5.6
2RS507/8DPT150 l /m6.5 bar2”1½”6409001357045401x240v2x1.52x2.02x6.3
2RS508/8DPT150 l /m7.0 bar2”1½”6409001357285401x240v2x2.22x3.02x8.2
2RS1002/8DPT320 l/m1.8 bar2½”2”6409501356275401x240v2x0.752x1.02x3.0
2RS1003/8DPT320 l/m2.5 bar2½”2”6409501356895401x240v2x1.32x1.82x5.6
2RS1004/8DPT320 l/m3.5 bar2½”2”6409501357085401x240v2x1.52x2.02x6.3
2RS1005/8DPT320 l/m4.0 bar2½”2”6409501357225401x240v2x2.22x3.02x8.2
2RS1006/8DPT320 l/m5.0 bar2½”2”6409501357395401X240V2x2.22x3.02x8.2

TRIPLE VARI-RS BOOSTER SPECIFICATIONS

vari-rs triple dimensions
Model RefMid Curve FlowMid Curve PressureDN1DN2BHH1LMPower SupplykWHPFLC (amp)
3RS302/8DPT150 l/m1.5 bar2½”2”9009201306085401x240v3x0.453x0.63x2.3
3RS305/8DPT150 l/m4.0 bar2½”2”9009201306565401x240v3x0.753x1.03x3.0
3RS306/8DPT150 l/m4.5 bar2½”2”9009201306805401x240v3x0.93x1.23x4.3
3RS307/8DPT150 l/m5.0 bar2½”2”9009201307045401x240v3x1.33x1.83x5.6
3RS308/8DPT150 l/m5.25 bar2½”2”9009201307285401x240v3x1.33x1.83x5.6
3RS502/8DPT225 l/m1.75 bar2½”2”9009201306275401x240v3x0.453x0.63x2.3
3RS505/8DPT225 l/m4.5 bar2½”2”9009201306895401x240v3x1.33x1.83x5.6
3RS506/8DPT225 l/m5.0 bar2½”2”9009201307085401x240v3x1.33x1.83x5.6
3RS507/8DPT225 l/m6.5 bar2½”2”9009201307225401x240v3x1.53x2.03x6.3
3RS508/8DPT225 l/m7.0 bar2½”2”9009201307395401x240v3x2.23x3.03x8.2
3RS1002/8DPT480 l/m1.8 bar2½”2”9009201306765401x240v3x0.753x1.03x3.0
3RS1003/8DPT480 l/m2.5 bar2½”2”9009201307255401x240v3x1.33x1.83x5.6
3RS1004/8DPT480 l/m3.5 bar2½”2”9009201307605401x240v3x1.53x2.03x6.3
3RS1005/8DPT480 l/m4.0 bar2½”2”9009201308345401x240v3x2.23x3.03x8.2
3RS1006/8DPT480 l/m5.0 bar2½”2”9009201308585401X240V3x2.23x3.03x8.2

contact us now with your requirements

your requirements

Please fill out the form below so we can accurately quote for your system requirements.

Why do we need this information?

For us to be able to calculate a booster set correctly we need to understand the number of outlets in your property that will be drawing pressure from the system. Once we have this information we can then calculate the number of “Loading Units” required required for your system. from here we can then determine the total pressure and litres per minute your booster set will need to deliver.

Alternatively, if you want to take a look at some of the most commonly asked questions then you can check out our FAQ’s below.