maxi grp package pump station range

The Maxi GRP package pump station is designed to collect foul or surface water from multiple properties, buildings or commercial offices and other industrial sized commercial applications.

These systems can store large volumes of waste / water without the need for a deep traditional vertical chamber type system. These systems are built to order, they can be manufactured to suit site specific requirements, such as taller turrets to pick up deeper incoming drains, and also precise measurements for the inlet depths can be pre-cut if the client requires.

product applications

Hospitals

HOSPITALITY

COMMERCIAL

INDUSTRIAL

PICKUP

Product ready for collection within 2-3 weeks

Delivery

Product shipped nationwide in 2-3 weeks

Support

Product support available between 8:30am -5pm

  • Huge choice of pumps
  • Sturdy GRP construction
  • Vertical and horizontal options
  • Built for demanding projects

product features

  • GRP chamber designed for extra strength
  • Single or twin vortex pumps with solid handling up to 50mm
  • Macerator pump available
  • 1 Year warranty (terms apply)
  • Non-return valve and internal pipework included
  • Ideal for sewage and grey water application 
  • Can be paired with high-level alarms and telemetry systems

MAXI GRP SPECIFICATIONS

Pump ChamberCapacity LitresTurret Height (mm)Inlet Invert Depth (mm)Diameter (mm)Length (mm)Inlet Diameter
H60006000300Variable18002900160
H80008000300Variable18003350160
H1000010000300Variable18004230160
H1200012000300Variable18005070160
H1400014000300Variable18005800160
H1600016000300Variable18006600160
H1800018000300Variable18007160160
H2000020000300Variable25004800160
H2500025000300Variable25005540160
H3000030000300Variable25006550160
H4000040000300Variable25008600160
H5000050000300Variable250011000160

MAXI PUMP SPECIFICATIONS

Model Ref6VX10VXMC
Impeller TypeVortexVortexMacerator
Power Supply230v 1ph 50hz230v 1ph 50hz230v 1ph 50hz
Rated Power0.3kW0.75.kw1.2kW
Rated Current1.9A4.0A9.2A
Max Head6M10M16M
Max Flow Rate5.5 l/s7.9 l/s1.8l/s
Cable Length10m10m10m
Free Passage50mm50mmMacerator
Model Ref65VX80VX
Impeller TypeVortexVortex
Power Supply230 - 1ph - 50hz230 - 1ph - 50hz
Rated Power1.5kW1.5kW
Rated Current12.0A11.2A
Max Head8m10m
Max Flow Rate10.0 l/s14.0 l/s
Cable Length10m10m
Free Passage65mm85mm

contact us now with your requirements

your requirements

Please fill out the form below so we can accurately quote for your system requirements.

Why do we need this information?

For us to be able to calculate a pump station correctly we need to understand a few key points of information. Please use the form to the left to help us quote for your project.

Key 

Rising Main – distance from the chamber to the sewer (meters)

Head – The height from the bottom of the chamber to the sewer

People – The maximum occupancy of the property

Application – Please state if this is for foul or surface water